Commercial HVAC Condensate Management in Roanoke, TX

TrueServ Mechanical completed a commercial HVAC condensate management project involving 56 fan-coil units at a commercial facility in Roanoke, Texas. The work focused on improving condensate drainage, strengthening overflow protection, and supporting reliable HVAC operation throughout the facility.

Project Details

FACILITY TYPE     

Commercial Facility

PROJECT TYPE

HVAC Condensate Management Rework

EQUIPMENT

56 Fan-Coil Units

LOCATION

Roanoke, TX

PROJECT COMPLETION

2026

Completed fan-coil condensate management rework.
Commercial Kitchen: Completed fan-coil condensate management rework

Project Overview

Condensate Management Upgrades for 56 Commercial HVAC Units

Proper condensate management helps protect commercial facilities from water damage caused by drainage problems, overflowing drain pans, and equipment malfunctions.

For this project, TrueServ Mechanical addressed multiple components of the existing drainage systems. Technicians improved condensate-pump positioning, corrected drain-line routing, reinforced auxiliary drain-pan supports, and integrated overflow-safety controls.

The work required careful coordination around existing equipment and ceiling spaces, including concealed fan-coil installations in kitchen and conference room areas.

Upon completion, each unit was individually inspected and documented as part of TrueServ’s quality-control process.

Project Highlights

TrueServ Mechanical completed the following condensate-management improvements:

Condensate pump properly mounted outside the auxiliary drain pan.
Conference Room: Condensate pump mounted outside auxiliary drain pan
  • Relocated condensate pumps from inside auxiliary drain pans.

  • Rerouted fan-coil drain lines.

  • Rerouted and secured condensate-pump discharge hoses.

  • Wired drain-pan overflow switches and internal pump overflow switches in series.

  • Installed rigid drain-pan supports and established proper slope toward overflow switches.

  • Insulated condensate piping with 1-inch-wall elastomeric insulation.

  • Replaced and dated final air filters supplied by the mechanical contractor.

  • Cleaned slope-related debris from work areas.

  • Inspected and documented all 56 fan-coil units at completion.

More Project Photos

The photographs throughout this case study show representative fan-coil units and condensate-management improvements from the completed 56-unit project.

Orange ladder providing ceiling access to concealed commercial HVAC fan-coil units in Roanoke, TX.
Commercial Kitchen: Concealed Fan-Coil Access
Supported auxiliary condensate drain pan beneath a commercial HVAC fan-coil unit in Roanoke, TX.
Commercial Kitchen: Supported & Properly Sloped Auxiliary Drain Pan
Commercial HVAC fan-coil filter replacement and dated unit documentation in Roanoke, TX.
Commercial Kitchen: Final Filter Replacement & Unit Documentation
Insulated condensate drain line and pump assembly on a Daikin commercial HVAC fan-coil unit in Roanoke, TX.
Conference Room: Insulated Condensate Drain Line
Condensate pump and insulated drain-line routing on a commercial HVAC fan-coil unit in Roanoke, TX.
Commercial Kitchen: Condensate Pump & Drain-Line Routing
Integrated condensate drain-pan and pump overflow safety controls on a commercial HVAC fan-coil unit in Roanoke, TX.
Commercial Kitchen: Integrated Drain-Pan & Pump Overflow Safeties
Condensate drain-pan and pump overflow safety connections on a commercial HVAC fan-coil unit.
Conference Room: Pump & Drain-Pan Safeties Wired in Series

Need Commercial HVAC Condensate Management Solutions?

From condensate drainage improvements and overflow protection to multi-unit HVAC system upgrades, TrueServ Mechanical helps commercial facilities protect their equipment, prevent water damage, and maintain reliable operation throughout Dallas-Fort Worth.